Main switch tripping on your busiest days? Check power factor before you upgrade
A main switch trips when the current through it stays too high for too long. Part of that current may be reactive current that does no useful work. Correcting power factor, now often done with a static VAR generator instead of capacitors, lowers that current and can buy headroom before you spend on a bigger supply.
It's the worst time for it. A hot Saturday, the venue is full, the kitchen is flat out and the air-con is working hard. Then the main switch trips.
The usual answer is a bigger supply: a new main switch, heavier cables, maybe a network upgrade. Those can be the right fix. But they're slow and costly, so it's worth checking first whether part of the current on your switchboard is doing no work at all.
Why a main switch trips
A main switch is sized to carry a set current, for example 630 amps per phase. Its protection allows short spikes, like a motor starting. What trips it is current that stays too high for too long.
So the question is how much of that current you really need.
The current that does no work
Motors, compressors, cool rooms, lifts and air-con draw two kinds of current:
- Working current - the part that actually runs the equipment. This is what your kWh measure.
- Reactive current - the part that builds the magnetic fields motors need. It flows back and forth without doing any work, but your cables and main switch still carry it.
Power factor tells you the mix. At 1.0, all the current is working current. At 0.90, your switchboard carries about 10% more current than the work needs. At 0.85, about 15% more.
On a quiet day that doesn't matter. On a day when you're running a few percent over the limit, it can be the difference between tripping and not.
How correction gives you headroom
Power factor correction supplies the reactive current on site, right at the switchboard, so it doesn't have to come through the main switch. The work still gets done, with less current coming in.
Take a site whose busiest phase reaches 670 amps on a hot day, against a 630 amp limit. If its power factor is 0.90 and correction brings it to 0.99, that phase drops to about 610 amps. If the power factor is already 0.95, correction only gets it to about 643 amps, which isn't enough on its own.
That's why the first step is always to measure.
The new way to do it
Power factor correction used to mean a cabinet of capacitors, switched in and out in steps. They work well on steady loads, but they react in seconds and they wear out.
The newer option is a static VAR generator (SVG). It's an electronic unit, a bit like a solar inverter, that measures your current thousands of times a second and makes exactly the reactive current needed:
- It reacts in milliseconds - so it keeps up with a kitchen, cool rooms and air-con cycling on a busy afternoon.
- It has no steps - so it holds close to 0.99 instead of over- and under-correcting.
- It can balance the phases - which lowers the current on the busiest phase, the one that trips.
- It's compact - modules mount on a wall and can be added to later.
Our guide to static VAR generators explains how they work, how to size one and how they compare with capacitor banks.
Don't pay demand charges on wasted current
Not your kWh. Your meter counts only working power, so correction barely changes your energy use, and the unit itself uses a little power.
Where it can lower the bill is a kVA demand charge. Many larger business tariffs, such as Endeavour Energy's N19, bill your peak in kVA, which includes the reactive part. Our power factor guide shows which tariffs bill kVA. Any saving is an estimate and depends on your power factor during the peak window.
For a site that trips, though, the bigger prize is usually avoiding or delaying the upgrade.
What to check first
- Your power factor - some bills show it, or show kVA next to kW. A logger at the main switchboard tells you properly.
- Your busiest days - log for a week or two, including the busy days, not just a quiet week.
- Phase balance - if one phase runs well above the others, moving single-phase loads may help before any equipment.
- Harmonics - a high neutral current usually points to harmonics, which need a different fix: an active harmonic filter.
- Your tariff - if it bills kVA, there's a bill saving on top of the headroom.
If power factor is already good, correction won't solve the trips. Then the options are moving load out of the peak, a battery to shave the peak, or the supply upgrade.
Get a free look at your site
We help businesses with power and gas, and we design and project-manage energy upgrades, from power factor correction to solar and batteries, with licensed partners doing the install.
If your main switch is tripping, send your latest bills to bills@omnienergysolutions.com.au or call us on 0433 679 324. We'll tell you what to measure, and whether correction, a battery or an upgrade is the right fix.