EA305: LV 160-750 MWh
What EA305 charges, when it applies, and what it means for solar and batteries.
Tell us a little about your site. The team will reply within 1 business day.
Get my free savings checkBook a 15-min callor call 0433 679 324A capacity charge in kVA based on your highest half hour between 3pm and 9pm on working weekdays over the last 12 months. For many sites it's the largest network charge on the bill.
Who's on EA305
Low voltage business sites using 160 to 750 MWh a year, such as factories, cold stores and larger venues.
EA305 rates for 2026-27
| Charge | Rate | Unit |
|---|---|---|
| Network access | 2546.5371 | c/day (about $9,295 a year) |
| Energy, peak | 8.2347 | c/kWh |
| Energy, off-peak | 1.8459 | c/kWh |
| Capacity | 57.7962 | c/kVA/day |
Network charges only, excluding GST. Your retailer adds its own energy rates, and may package these charges differently. Rates apply from 1 July 2026 to 30 June 2027.
When each charge applies
Capacity is measured 3pm to 9pm on working weekdays, all year. Peak energy applies 3pm to 9pm on working weekdays, from November to March and June to August.
50 kVA x 57.80c x 365 days$10,548 a yearOnly if the lower peak holds on every working weekday for a full 12 months. Before battery or equipment costs. Illustrative only.
If you add solar
Solar lowers daytime energy, but your capacity peak can land after the sun has dropped. Check when your highest half hours happen before counting on a capacity saving.
If you add a battery: fit depends on your peaks
The prize is large, and so is the risk. A battery has to catch the peak on every working weekday for 12 months, and one miss can reset the charge for a year. See how battery peak shaving works.
What to check
Because this tariff bills kVA, poor power factor inflates the charge. Check power factor before you price a battery.
Find out if it's worth doing on your site
Send us what you have. We'll tell you whether it's worth doing, marginal or not worth it.
- Your latest billPower and gas if you have both. A photo is fine.
- 12 months of half-hourly dataWith your sign-off, we can request it for you.
- Anything that's changingExisting solar, new equipment, EV chargers or extra shifts.
From sites we've worked on
Common questions
How is the EA305 capacity charge worked out?
Ausgrid takes your highest half-hour kVA reading between 3pm and 9pm on working weekdays over the previous 12 months, then charges 57.7962c per kVA per day.
Can the EA305 capacity be reset?
Ausgrid will consider a reset, once a year, after a permanent reduction such as power factor correction. Your retailer applies, with evidence.
See what you could save